CHECKLIST (General)
SEE ATTACHMENTS
FOR ADDITIONAL INFORMATION
NOTE: This
checklist is designed to inventory a pole from top to bottom.
►
(Pole ground 4 or 8 per mile) Rule 96C & 92D
→Identify Button Info #________ _________ ___________
→Identify phases __ 1 ph ___ 2 ph
___ 3 ph ___Other _________________
→Identify conductor’s ______________________
→Identify Neutral _____________________
→Identify Equipment (transformers) most are
single phase _______amps?
○ □
Verify Equipment is grounded.
○ □
Verify Equipment ground bonding and bonding location.
( ) Bonded to Neutral (Transformer ground to
neutral)?
( ) Bonded to Ground wire (Equipment ground to
ground)?
○ □
Verify other Equipment, (cutouts, etc. Arresters to ground).
NOTE: EQUIPMENT must be GROUNDED / BONDED
TRANSFORMER MUST BE GROUNDED TO GROUND ROD.
→Identify Secondary’s
○ □ Secondary Crossover roads, sidewalks, driveways, ___16 ft
_______ Other Rule 230C2) 232(1)
○ □
Clearance yards, ____12 ft ______ Other Rule 230C
○ □
Verify Secondary Rack to ground wire (bonded)
→GUY/INSULATOR/GUARDS
○ □
Verify Guy grounding / Insulated Rule 92C2
○ □
Verify Insulators attached (as required) If guy wire is close or crossover Primary,
Secondary, Equipment.
○ □
Verify guards are installed as necessary. (Public access) Rule 93D2
○ □
Verify Insulators are installed a minimum of 8 ft from
ground. Rule 279A2 (b) (1)
→Identify Street Lights (as applicable)
○ □
Verify Secondary source to requirements (2”) Rule 238D
□ Verify Grounding and bonding. Rule
230C(3)
ATTACHMENTS
→Identify Vendor attachments ( _____Cable, ____Teleco,
_____ Fiber, )
○ □
Verify Attachment clearance to lowest power source on pole (Primary
or Secondary) (40”) Rule 238B
○ □
Verify Attachment along roads/ Crossover roads/alleys/commercial
driveways ______ 15.5 ft.
Rule230E1(24)
○ □ Verify Attachment, over residential driveways, ___11.5 ft _______ Other
Rule 232A & 232-1
○ □
Verify Attachment Clearance sidewalks, yards, house
attachment, ____9.5ft ______ Other Rule 232-1
NOTE: Street
light power source (exceptions)
○ □
Verify clearances between attachments. (12”) See exceptions if applicable Rule 235C(1) ex(3)
○ □
Verify grounding of attachment messengers. Bonding Rule 92C3
GROUNDING
○ □
Verify ground wire to ground rod.
○ □
Verify ground rod below top of ground Rule 94B2
RISER
○ □
Verify Secondary from/to top of Riser is 40” clearance from
communication cables Rule 236E &
235C1
○ □
Verify bottom Riser attachment are separated 8 ft apart.
Minimum Rule 217A2(c)
○ □
Verify ground of Riser (as required) Rule 239D
POLE
○ □
Verify setback of 6” from edge of street (curb) ______
Rule 231B(1)
○ □
Verify pole steps 8 ft above ground Rule 217A & 239D
MID-SPAN
○ □
Verify Cable to Cable clearance 12”. (See exceptions) Rule 235C1 & 235H
Communication clearance from Neutral / Secondary - __30”
____ Other Rule 232B1
SPECIAL CLEARANCES
○ □
Verify RAILROADS _______23.5 ft. Exception _______26.5 FT. Rule 231C
○
□ Verify Fire hydrants
_______4’ft. Exception
_______3’ FT Rule 231A